The cabinet is designed for distribution of alternating current heating of the switch and power supply of the switching coil and for outdoor installation on open distribution devices of power plants and substations. The equipment is designed for use in an industrial atmosphere and has a protective coating that ensures long-term operation under the influence of climatic factors of external environment. The switch cabinet can be used for:
The device functionally consists of:
Overall dimensions of the device:
|
Technical characteristics:
Characteristic | Value |
View, frequency current |
AC, 50Hz |
Rated current |
250А |
Rated working voltage of main circuit |
380V, AC |
Rated auxiliary circuit voltage |
220V AC, 50Hz |
Rated main circuit insulation voltage |
500V |
Rated auxiliary circuit insulation voltage |
500V |
Full shut-off current of waste vending machines |
Icu=6kА |
Degree of protection |
IP54 |
Grounding system |
TN-S |
Type of internal separation |
1 |
Type of electrical connections of functional units | FFF |
Design of the circuit-breaker heating cabinet:
The device consists of a solid metal steel body with a partition in shape 1. The door is fitted with a lockable lock.