The DC panel provides uninterrupted power supply to control circuits, relay protection, automation, and signaling systems at electrical stations/substations during grid outages by automatically switching to backup battery power. When main power is restored, it automatically charges batteries while simultaneously powering loads. Designed for industrial environments.

Technical Specifications:
 
Parametr Value
Input Voltage/Frequency 
380/220V, 50Hz
Main Circuit Insulation Voltage
500V
Auxiliary Circuit Insulation Voltage
500V
Charger Output Voltage 
220V
Current Type 
Direct current
Charger Type 
PBI MC
Charger Output Current 
2x20А 
Charger Redundancy
2 parallel units with hot-swappable
Battery Capacity 60A/h
Feeder Auto-Disconnect (Quantity)
20 pieces
Insulation Monitoring
PBI MC
Flashing Light Device
Switching pulse-pair D-28
Instruments 
Мoltmeter, ammeter
Protection Rating (IP)
IP 31
Communication Protocol  По интерфейсу RS485: Mobilus RTU / IEC60870-5-103 / APS6000
 

 

 

Functional Composition:

  • ATS power circuits;
  • Battery charge/discharge & DC distribution circuits;
  • Flashing bus circuits;
  • Alarm circuits;
  • Voltage/current monitoring circuits.

Structural Composition:

  • Charger Panel;
  • Distribution Panel;
  • Battery Panel.

Key Functions:

  • DC power distribution for auxiliary systems;
  • Power supply via rectifiers/batteries during outages;
  • Personnel safety protection;
  • Overvoltage protection for distribution buses;
  • Secondary circuit protection;
  • Protection device status monitoring;
  • Parameter deviation alarms;
  • LED status/event indicators;
  • Continuous DC insulation resistance monitoring; 
  • SCADA integration for system status.

 

 

 

Structure:

The device consists of a frame metal structure covered with powder paint to prevent the appearance of corrosion, with a partition in form 1. For access to the shield from the front side there are doors that are locked by a key. In the lower part of the body of the device, a PE grounding bus is installed. The cable entry and connection is carried out in the upper part of the shield.  The device fully meets the requirements of standard RT RC GOST P 51321.1-2010 (IEC 60439-1-92).

Common characteristics:
 
Construction of the body  Foor
Color RAL 7035
Accession entry 
from below, from above
Degree of protection IP 54
Seismic resistance according to MSK-64 scale from 6 to 9 points
Method of service
одностороннего/ двухстороннего 
Number of modules for charging and rectifying devices to 4 units
Battery capacity, A/h  to 190